Page #143 background image
Chapter 8 Built-in High-speed Counter Function
(g) The example that number of pulse per 1 revolution set to 10 and time is set to 60,000 ms
is as shown below.
(7) Count latch
When Count latch signal is On, present count value is latched.
Setting
If present counter value is to latch, Count Latch function is set Use.
Class
Device area per channel
Operation
Ch.0
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Count latch
command
%KX4166 %KX4326 %KX4486 %KX4646 %KX34886 %KX35046
%KX35206
%KX3536
6
0: disable
1: enable
Count latch function is operated when Count latch signal is On. Namely, counter value is not
cleared when power supply Off =>On and mode change, it is counted from previous value.
In latch counter function, internal or external preset function has to use for clearing present
value.
Command
Count value
1000
500
0
300
400
700
500
350
Revolution
per time
60000 60000 60000 60000
10
30
20
15
8-19