3. From the DCD-523, cross connect terminals (two audible major alarms), connect
to an available pair of scan leads from the MMSU. Record scan point used for the
major alarm connection.
4. Select and prepare terminal for RC/V activities.
Note: The identification of the scan points should be known before continuing
with the RC/V activity.
5. To provision the first alarm scan point, at the RC/V terminal, type and enter:
8.11i
Response: The REMOTE ALARM ASSIGNMENT page is displayed. The cursor
is positioned at the REMOTE MODULE field.
6. To assign alarms, type and enter data for the following fields:
REMOTE MODULE ____
ALARM POINT _____ (000–054, refer to completed 8.11 form for assignment)
SCAN POINT = aaabcddee
Where: aaa = Switching module number
b = Metallic service unit (MSU) number, 0,1
c = MSU service group, 0,1
dd = MSU board number, 00-31
ee = MSU scan point number, 00-31.
Response: Enter Insert, Change, Validate, or Print:
7. To insert, type and enter:i
Response: inserting...FORM INSERTED.
8. Repeat Steps 6 and 7 to insert additional scan point.
9. With all scan points assigned, exit RC/V.
10. To backup ODD, at the MCC, type and enter:
BKUP:ODD,NRODD=a,RODD,AM;
Where: a = Switching module number.
Note: Prior to the response, there will be completed responses for the switching
module and the AM.
Response: BKUP NRODD COMPLETED
Note: Database backup will take several minutes to complete.
5.11.5.4 Test BITS Box Alarms
1. Disconnect one of the input clocks from the BITS box.
Response: A MINOR alarm output message is generated.
MINOR alarm LED on the BITS Box SAI/MTS card is lighted.
2. Reconnect the clock input that was disconnected in the previous Step.
3. At the BITS Box press the ACO switch on the SAI/MTS card to clear the MINOR
alarm.
Response: MINOR alarm LED on the BITS box SAI/MTS card is off.
235-200-150
January 2003
ROUTINE MAINTENANCE
Procedure 5.11
Issue 3.00 Page 5.11-7