(c) Type and enter: i
Note: An error message will be displayed if you have a physical TTY with
the same TTY letter as the VTTY being grown. Select another VTTY or
degrow the physical TTY. Refer to 235-105-331, 5ESS Switch Hardware
Change Procedures — Degrowth or 235-600-315, 5ESS Switch ECD/SG
Database Manual.
(d) First prompt: Remove VTTYC/VTTY x from service. Enter CARRIAGE
RETURN to continue. At DRM MCC terminal, type and enter command:
RMV:[VTTYC,VTTY]=x
Where: x = VTTYC/VTTY number of the previous logical unit.
Response: RMV [VTTYC,VTTY] x COMPLETED
(e) Second prompt: Restore VTTYC/VTTY x to service. Enter CARRIAGE
RETURN to continue. At DRM MCC terminal, type and enter command:
RST:[VTTYC,VTTY]=x
Where: x = VTTYC/VTTY number of the previous logical unit.
Response: RST [VTTYC,VTTY] x COMPLETED
(f) Third prompt: Restore VTTY x to service. Enter CARRIAGE RETURN to
continue. At DRM MCC terminal, type and enter command: RST:VTTY=x
Where: x = appropriate VTTY number.
Response: RST VTTY x COMPLETED
(g) The low-level forms will now be added automatically.
Response: FORM INSERTED
4. Exit high-level forms.
(a) Type and enter: <
Response: Exit the vttyadd form UNIX RTR RCV (ODIN) - Data Entry
page displayed. Cursor at Enter Form Name:
(b) Type and enter: toggle
Response: Will take you to the low-level forms.
5. Backup Incore ECD to disk.
(a) Type and enter: activate
Response: Activate form displayed with cursor at 1.copy_inc_to_disk:YES
(b) Enter CARRIAGE RETURN
Response: ODIN will request the action desired.
(c) Type and enter: e
Response: ODIN returns to the UNIX RTR (ODIN) - Data Entry page.
(d) Type and enter: <
Response: RCV ECD COMPLETED
6. Change Security (optional).
235-200-150
January 2003
GROWTH AND DEGROWTH
Procedure 8.1
Issue 3.00 Page 8.1-3