IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-77
F01-26 PG Deviation Sel Stopping method at excessive
speed deviation.
Traverse: 0–7
NLB: 5
5VG+
0 @Spd Agree-
Decel
Stops by deceleration time 1 -
B05-02.
1 @Spd Agree-
Coast
Coast to stop.
2 @SpdAgree-F-
Stop
Decelerates by fast-stop B05-08.
3 @Spd Agree-Alm DEV displayed, operation
continues.
4 @Run-Decel Stops by deceleration time 1 -
B05-02.
5 @Run-Coast Coast to stop.
6 @Run-Fast Stop Decelerates by fast-stop B05-08.
7 @Run-Alarm Only DEV displayed, operation
continues
F01-27 PG Deviate Level Sets the speed deviation
detection level as a percentage
of the maximum output
frequency.
0–50% 10 VG+
F01-28 PG Deviate Time Sets the time in seconds for a
speed deviation situation to
trigger a fault DEV.
0.0–10.0 sec 0.3 VG+
Parameter Display Function Range Default Model