Interface CAN-2 touch display
140
Read this manual carefully before starting any work!
This is particularly applicable to the chapter “General Safety Instructions”
and the respective safety instructions in the chapters.
18.2.2 EEC2
Transmission repetition rate: 50 ms
Data length: 8 bytes
Identifier: 0x0C F0 03 27
Byte 1: Default Value = 0xFF
Not supported
Byte 2: Throttle position
0.4 % per bit
0 % offset
Range: 0 % ... 100 %
SAEJ1939-71: SPN 91
Byte 3: Load at current speed
1 % per bit
0 % offset
Range: 0 % ... 125 %
SAEJ1939-71: SPN 92
Byte 4 - 8: Default Value = 0xFF FF FF FF FF
Not supported
18.2.3 Turbocharger Info 4
Transmission repetition rate: 500 ms
Data length: 8 bytes
Identifier: 0x18 FE 98 27
Byte 1, 2: Exhaust temperature before turbo 1
0.03125 °C per bit
-273 °C offset
Range: -273 °C ... 1735 °C
SAEJ1939-71: SPN 1180
Byte 3, 4: Exhaust temperature before turbo 2
0.03125 °C per bit
-273 °C offset
Range: -273 °C ... 1735 °C
SAEJ1939-71: SPN 1181
Byte 5 - 8: Default Value = 0xFF FF FF FF
Not supported