APPENDICES APPENDIX
Appendix 7 Setting Examples
487
A
■When accessing from an Ethernet interface module
When accessing a multidrop connection station with the frames (4E frame, 3E frame) for the Ethernet interface module,
specify the start input/output number of a multidrop connection source module (relay station) and the station No. of an access
target to the request destination I/O No. and the request destination module station No. For the request destination I/O No.,
specify the value obtained by dividing the start input/output number by 16 in 4 digits (hexadecimal).
The following shows the setting example of the cases below.
• Multidrop connection source module of the relay station: Start input/output number 0050H (request destination module I/O
No.0005H)
• Multidrop connection station of the access target: Station No.1
: Unnecessary
Accessing via network
When accessing other stations via network, specify the network No. and station No. of an access target network module to the
network No. and PC No.
The following shows setting examples for accessing other stations via network (network No. 1, station No.2) without a
multidrop connection.
: Unnecessary
Access target Frame Station No. Network No. PC No. Request
destination
module I/O No.
Request
destination
module station
No.
Self-
station
No.
Multidrop connection station 4E/3E 00 FF 0005 01
Access target Frame Station No. Network No. PC No. Request
destination
module I/O No.
Request
destination
module station
No.
Self-
station
No.
Other station via network
•Network No.1
• Station No.2
4C 00 01 02 03FF 00 00
3C 00 01 02 00
4E/3E 01 02 03FF 00
Other station accessed
via the network module
set in the "Valid Module
During Other Station
Access" setting.
• Station No.2
4C 00 FE 02 03FF 00 00
3C 00 FE 02 00
1C 00 02
4E/3E FE 02 03FF 00
1E 02
E71
C24
External device
Multidrop connection
Connected station
(Host station)
:Station specified to the request destination module I/O No.
:Access target station
(Station specified to the request destination module station No.)
StationNo.1
Startinput/outputNo.0005
(Relaystation)
Network
No.1
:Access target station
(Station specified to the network No. and PC No.)
Other stations
External device
Connected station
(Host station)
Station No.2