488
APPENDICES APPENDIX
Appendix 7 Setting Examples
Connecting with a multidrop link and via network
The following shows setting examples for connecting with a multidrop connection and via network.
Other stations via network from a multidrop connection
Specify the setting for a multidrop connection including the connected station (host station) and the setting for a connection
via network each.
Specify the station No. of a multidrop connection station for a relay to the station No.
Specify the network No. and station No. of an access target to the network No. and PC No.
The following shows the setting example of the cases below.
Multidrop connection station of the relay station: Station No.1
Network module of the access target: Network No.1, station No.2
: Unnecessary
Multidrop connection station via network
For accessing a multidrop connection station in the target via network, specify the start input/output number of a multidrop
connection source module and the station No. of an access target to the request destination module I/O No. and the request
destination module station No. For the request destination module I/O No., specify the value obtained by dividing the start
input/output number by 16 in 4 digits (hexadecimal).
Specify the network No. and station No. of a network module for a relay station to the network No. and PC No.
The following shows the setting example of the cases below.
Network module for the relay station: Network No.1, station No.2
Multidrop connection source module of the relay station: Start input/output number 0050H (request destination module I/O
No.0005H)
Multidrop connection station of the access target: Station No.1
: Unnecessary
Access target Frame Station No. Network No. PC No. Request
destination
module I/O No.
Request
destination
module station
No.
Self-
station
No.
Other stations via
network from a multidrop
connection
4C 01 01 02 03FF 00 00
3C 01 01 02  00
Access target Frame Station No. Network No. PC No. Request
destination
module I/O No.
Request
destination
module station
No.
Self-
station
No.
Multidrop connection
station via network
4C 00 01 02 0005 01 00
4E/3E 01 02 0005 01
External device
Multidrop connection
Other stations
Network
No.1
(Relay station)Connected station
(Host station)
:Station specified to the station No.
:Access target station
(Station specified to the network No. and PC No.)
Station No.2
Station No.1
External device
Multidrop connection
Connected station
(Host station)
Network
No.1
:Station specified to the request
destination module I/O No.
(Relay station)
:Access target station
(Station specified to the request
destination module station No.)
:Station specified to the network No.
and PC No.
Station No.2
Station No.1
Start
input/output No.
0005