8 Troubleshooting NICE7000 User Manual
- 212 -
Fault
Code
Name Possible Causes Solution Level
Err22
Leveling signal
abnormal
101: The leveling
position deviation is too
large in elevator auto-
running state.
101:
Check whether the leveling and
door zone sensors work properly.
Check the installation verticality
and depth of the leveling plates.
Check the leveling signal input
points of the MCB.
Check whether the steel rope
slips.
1A
Err24 RTC clock fault
101: The RTC clock
information of the MCB
is abnormal.
101:
Replace the clock battery.
Replace the MCB.
3B
Err25
Storage data
abnormal
101, 102:
The storage data of the
MCB is abnormal.
101, 102:
Contact the agent or Monarch.
4A
Err26
Earthquake
signal
101: The earthquake
signal is active and the
duration exceeds 2s.
101: Check that the earthquake
signal is consistent with the
parameter setting (NC, NO) of the
MCB.
3B
Err29
Shorting
PMSM stator
feedback
abnormal
101: The shorting
PMSM stator feedback
is abnormal.
101:
Check that the state (NO, NC)
of the feedback contact on the
contactor is correct.
Check that the contactor and
corresponding feedback contact
act correctly.
Check the coil circuit of the
shorting PMSM stator contactor.
5A
Err30
Elevator
position
abnormal
101, 102:
In the normal-speed
running or re-leveling
running mode, the
running time is smaller
than the smaller of F9-
02.
101, 102:
Check whether the leveling signal
cables are connected reliably and
whether the signal copper wires
may touch the ground or be short
circuited with other signal cables.
Check whether the distance
between two oors is too large,
causing too long re-leveling
running time.
Check whether signal loss exists
in the encoder circuits.
4A