Section 75 00-02-0878
2013-03-07 - 95 -
Condition Comment Note
MAINS FAILURE IN ###s Frequency or voltage measurement is outside the limits
The timer shown is
the Mains failure
delay. Text in mains
units
MAINS U OK DEL ####s Mains voltage is OK after a mains failure
The timer shown is
the Mains OK delay
MAINS f OK DEL ####s Mains frequency is OK after a mains failure
The timer shown is
the Mains OK delay
Hz/V OK IN ###s The voltage and frequency on the genset is OK
When the timer runs
out it is allowed to
operate the
generator breaker
COOLING DOWN ###s Cooling-down period is activated
COOLING DOWN Cooling-down period is activated and infinite
Cooling down timer
is set to 0.0 s
GENSET STOPPING This info is shown when cooling down has finished
EXT. STOP TIME ###s
EXT. START ORDER A planned AMF sequence is activated
There is no failure
on the mains during
this sequence
QUICK SETUP ERROR Quick setup of the application failed
MOUNT CAN
CONNECTOR
Connect the power management CAN line
ADAPT IN PROGRESS
The EMS-GC10 is receiving the application that it has
just been connected to
SETUP IN PROGRESS
The new EMS-GC10 is being added to the existing
application
SETUP COMPLETED
Successful update of the application in all EMS-GC10
units
REMOVE CAN
CONNECTOR
Remove the power management CAN lines
PREPARING ENGINE IF Preparing engine IF
PROGRAMMING M-
LOGIC
Downloading M-Logic to the unit