Section 75 00-02-0878
2013-03-07 - 154 -
Mtu Smart Connect
Alarms, status and measurement table (read only) function code 04h.
Addr. Content Type
1020 EIc alarms
Bit 0 7570 EIC communication error
Bit 1 7580 EIC warning
Bit 2 7590 EIC shutdown
Bit 3 7600 EIC overspeed
Bit 4 7610 EIC coolant water temp. 1
Bit 5 7620 EIC coolant water temp. 2
Bit 6 7630 EIC oil pressure level 1
Bit 7 7640 EIC oil pressure level 2
Bit 8 7650 EIC oil temp. 1
Bit 9 7660 EIC oil temp. 2
Bit 10 7670 EIC coolant level 1
Bit 11 7680 EIC coolant level 2
1024 EIC alarms, engine controller (DM1)
Bit 0 EIC communication error
Bit 1 EIC yellow
Bit 2 EIC red
Bit 3 EIC protection
Bit 4 EIC malfunction