Section 75 00-02-0878
2013-03-07 - 98 -
Basic Parameter Settings
Set PIN code for GSM modem
Set phone no. for SMS to cellular phone 1
Set phone no. for SMS to cellular phone 2
Set phone no. for SMS to cellular phone 3
Set phone no. for SMS to cellular phone 4
Set phone no. for SMS to cellular phone 5
NOTE: For calling a
foreign
number
type
"+" and country code
instead
of "00", for
example dial +45
99999999 for
a Danish number.
NOTE:
The
phone number can only be entered using
the
PC
utility
software (USW).
NOTE: The SIM card used in the cellular telephone must support
data transfer.
PIN Code Configuration
After each auxiliary supply power up, the unit will send the required PIN code to the
modem if this is necessary. The PIN code is adjusted in the PC utility software (USW).
USW Remote Communication
It is possible to communicate with the unit via the PC utility software (USW). The
purpose is to be able to remotely monitor and control the genset application.
NOTE: It is possible to remotely control the genset from the PC
utility software (USW) if a modem is used. Take precautions that it
is safe to remotely operate the genset to avoid personal injury or
death.
Setup
The Modbus protocol type can be changed from RTU to ASCII. When set to ASCII
protocol, the unit will allow for the slower modem communication.
Application settings
Please refer to the PC utility software help file.
Safety
If communication fails, the unit will operate according to the received data. If for
example, only half of the parameter file has been downloaded when the communication
is interrupted, the unit will use this actual data.