Section 75 00-02-0878
2013-03-07 - 112 -
Error Messages
The following error messages can occur:
The view is not selectable for the present engine type.
Value selected error
The value cannot be read due to the sensor error, sub-system or
module error.
“N.A.”
The value is not supported by the engine, or due to a communication
error.
Object Selection, J1939
The view lines can be configured with these available values.
NOTE: For Modbus scaling, please see the chapter “Modbus
Communication”.
NOTE: The engine is expected to use source address 0.
Object PGN No.
Pri-
Ority
Posi-
Tion
Of 1
st
Data
Length
(Bytes)
SPN
No.
Unit J1939-71 Scaling
EIC speed 61444 3/6 4 2 190 RPM 0.125 rpm/bit, offset 0
65262 3/6 1 1 110 °C 1 deg C/bit, offset -40°C
65263 6 4 1 100 Kpa 4 kpa/bit, offset 0
EIC faults (4) 65230 6 1 1 1218 1/bit, offset 0
EIC oil temp. (3) 65262 3/6 3 2 175 °C 0.03125°C/bit, offset -273°C
EIC fuel temp. 65262 3/6 2 1 174 °C 1°C/bit, offset -40°C
manifold #1 P.
(also called EIC
65270 6 2 1 102 kpa 2 kpa/bit, offset 0
EIC air inlet temp. 65269 6 6 1 172 °C 1°C/bit, offset -40°C
EIC coolant level 65263 6 8 1 111 % 0.4%/bit, offset 0
EIC fuel rate 65266 6 1 2 183 l/h 0.05 l/h per bit, offset 0
manifold 1 temp.
(also called EIC
65270 6 3 1 105 °C 1°C/bit, offset -40°C
EIC d.d. % torque 61444 3/6 2 1 512 % 1%/bit, offset -125%
61444 3/6 3 1 513 % 1%/bit, offset -125%
pos.
61443 3/6 2 1 91 % 0.4%/bit, offset 0