Section 75 00-02-0878
2013-03-07 - 128 -
Iveco (J1939)
Warnings and Shutdowns
Warning/shutdown list
J1939
codes
SPN FMI warning FMI shutdown
Low oil pressure
100
17
1
Intake manifold #1 P
102
15
-
Coolant temperature
110
15
0
High inlet air temp.
172
15
-
Fuel temperature
174
15
-
Overspeed
190
15
0
EIC yellow lamp
-
X
-
EIC red lamp
-
-
X
EIC malfunction
-
X
-
EIC protection
-
X
-
NOTE: FMI indication “-“ means that the alarm in question is not
supported.
Write Commands to Engine Controller
Engine Controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls).
Engine Speed
CANbus ID for speed control: 0x0c000003.
For J1939 TSC1, the source address of the EMS-GC10 controller is 3.
For the Iveco Vector 8 type only: CANbus ID for speed control: 0xcFF0027.
M-Logic commands are available to enable/disable start/stop and speed controls:
EIC Speed Control Inhibit
NOTE: The speed regulation is enabled in parameter 2781 (Reg. output)
and 7563 (EIC Controls).