Section 75 00-02-0878
2013-03-07 - 127 -
Write Commands to Engine Controller
Engine Controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls).
Engine Speed
CANbus ID for speed control: 0x0c000003. For J1939 TSC1, the source address of
the EMS-GC10 controller is 3.
EIC Speed Control Inhibit
NOTE: The speed regulation is enabled in parameter 2781 (Reg. output)
and 7563 (EIC Controls).
Generic J1939 (J1939)
Warnings and Shutdowns
Warning/shutdown list
J1939
d
SPN
FMI warning
FMI shutdown
EIC yellow lamp
-
X
-
EIC red lamp
-
-
X
EIC Malfunction
-
X
-
EIC Protection
-
X
-
NOTE: FMI indication “-“ means that the alarm in question is not
supported.
Write Commands to Engine Controller
Engine Controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls).
Engine Speed
CANbus ID for speed control: 0x0c000000. J1939 TSC1.
M-Logic commands are available to enable/disable start/stop and speed controls.
EIC Speed Control Inhibit
NOTE: The speed regulation is enabled in parameter 2781 (Reg. output)
and 7563 (EIC Controls).

Table of Contents