Section 75 00-02-0878
2013-03-07 - 139 -
Volvo Penta EMS 2 (J1939)
EMS 2 and EDCIII/D6, D7, D9, D12 and D16 (GE and AUX variants only).
Warnings and Shutdowns
Warning/shutdown list
SPN FMI warning FMI shutdown
NOTE: FMI indication “-“ means that the alarm in question is not supported.
Write Commands to Engine Controller
• Engine Controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls)
• Engine Speed
CANbus ID for speed control: 0x0cff4611 – Volvo Penta proprietary telegram
M-Logic commands are available to enable/disable start/stop and speed controls:
• EIC start/stop enable
• EIC speed control inhibit
• Preheat
• Start/Stop
Readable States - Preheat and Running
NOTE:
The
speed regulation is enabled in
parameter 2781 (Reg.
output) and
7563 (EIC
Controls).
NOTE:
Selection
of
primary or secondary speed is
selected
in
parameter
2774.