Section 75 00-02-0878
2013-03-07 - 96 -
Counters
Counters for various values are included, and some of these can be adjusted if
necessary, for instance if the unit is installed on an existing genset or a new circuit
breaker has been installed.
The table shows the adjustable values and their function in parameter 6100:
Parameter and
Description
Function
Comment
6101
Running time
Offset
adjustment
of the total running
hours
counter.
Counting
when the running
feedback
is
present.
6102
Running time
Offset
adjustment
of the total running
thou
sand hours counter.
Counting
when the running
feedback
is
present.
6103 GB
operations
Offset
adjustment
of the
number
of
genera
tor
breaker operations.
Counting
at
each
GB
close
command.
6104 MB
operations
Offset
adjustment
of the
number
of
mains
breaker operations.
Counting
at
each
MB
close
command.
6105 kWh
reset
Resets
the kWh
counter.
Automatically resets
to
OFF
after
the
reset.
The reset function cannot
be left
active.
6106 Start
at
tempts
Offset
adjustment
of the
number
of start
at
tempts.
Counting
at
each
start
attempt.
NOTE: Additional counters
for
"Running hours" and "Energy" can
be
read
out
from the
PC
utility soft
ware (USW).
M-Logic
The M-Logic functionality is included in the unit and is not an option-dependent
function.
M-Logic is used to execute different commands at predefined conditions. M-Logic is not
a PLC but substitutes one, if only very simple commands are needed.
M-Logic is a simple tool based on logic events. One or more input conditions are
defined, and at the activation of those inputs, the defined output will occur. A great
variety of inputs can be selected, such as digital inputs, alarm conditions and running
conditions. A variety of the outputs can also be selected, such as relay outputs, change
of genset modes and change of running modes.
NOTE: The M-Logic is part of the PC utility software (USW), and
as such, it can only be configured in the PC utility software and not
via the display.