Section 75 00-02-0878
2013-03-07 - 84 -
34. MB spring loaded
EMS-GC10 genset controller unit will not send a close signal before this feedback is
present.
35. D+ (digital running feedback)
This input is used as a running indication of the engine. When the input is activated, the
start relay is deactivated. This is the input for running feedback from charge generator
+D terminal. (Runs when charger (voltage) U > battery voltage).
36. Inhibit EI alarms
When this input is active, it will inhibit all engine interface [(Engine Interface
Communication, (EIC) (J1939)] alarms.
NOTE: The input functions are set up with the PC utility software
(USW), please refer to "Help" in the USW for this.
Outputs
The unit has a number of output functions which can be configured to any available
relay.
Output Function
Auto
Semi
Test
Man
Block
Configurable
Output Type
1
Status OK
X
X
X
X
X
Configurable
Constant
2
Run coil
X
X
X
X
X
Configurable
Constant
3
Stop coil
X
X
X
X
X
Configurable
Constant
4
Prepare
X
X
X
X
X
Configurable
Constant
5
Starter (Crank)
X
X
X
X
X
Configurable
Constant
6
Horn
X
X
X
X
X
Configurable
Constant
7
GB on
X
X
X
X
X
Configurable
Continuous
8
GB off
X
X
X
X
X
Configurable
Continuous
9
MB on
X
X
X
X
X
Configurable
Continuous
10
MB off
X
X
X
X
X
Configurable
Continuous