Section 75 00-02-0878
2013-03-07 - 94 -
Text
in
Status
Line
This table explains the different messages in the status line text.
Condition Comment Note
BLOCK Block mode is activated
SIMPLE TEST
Test mode is activated
FULL TEST
SIMPLE TEST ###.#min
Test mode activated and test timer counting down
FULL TEST ###.#min
ISLAND MAN
Genset stopped or running and no other action taking
place
ISLAND SEMI
READY ISLAND AUTO Genset stopped in Auto
ISLAND ACTIVE Genset running in Auto
AMF MAN
Genset stopped or running and no other action taking
place
AMF SEMI
READY AMF AUTO Genset stopped in Auto
AMF ACTIVE Genset running in Auto
LOAD TAKEOVER MAN
Genset stopped or running and no other action taking
place
LOAD TAKEOVER SEMI
READY LTO AUTO Genset stopped in Auto in load takeover operation mode
LTO ACTIVE Genset running in Auto in load takeover operation mode
Generator stopped and active alarm(s) on the generator
GB ON BLOCKED
Generator running, GB open and an active "Trip GB"
alarm
SHUTDOWN OVERRIDE The configurable input is active
ACCESS LOCK
The configurable input is activated, and the operator tries
to activate one of the blocked keys
GB TRIP EXTERNALLY Some external equipment has tripped the breaker
logged in the event
MB TRIP EXTERNALLY Some external equipment has tripped the breaker
logged in the event
IDLE RUN
The "Idle run" function is active. The genset will not stop
until a timer has expired
IDLE RUN ###.#min The timer in the "Idle run"’ function is active
Aux. test ##.#V ####s Battery test activated
START PREPARE The start prepare relay is activated
START RELAY ON The start relay is activated
START RELAY OFF Start relay is deactivated during the start sequence
MAINS FAILURE Mains failure and mains failure timer expired