Section 75 00-02-0878
2013-03-07 - 155 -
MTU ADEC
Alarm, status and measurement table (read only) function code 04h.
Addr. Content Type
1020 EIC alarms
Bit 0 EIC 7570 communication error
Bit 2 EIC 7590 shutdown
Bit 3 EIC 7600 overspeed
Bit 4 EIC 7610 coolant water temperature 1
Bit 5 EIC 7620 coolant water temperature 2
Bit 6 EIC oil pressure 1
Bit 7 EIC 7640 oil pressure 2
Bit 8 EIC 7650 oil temp. 1
Bit 9 EIC 7660 oil temp. 2
Bit 10 EIC 7670 coolant level 1
Bit 11 EIC 7680 coolant level 2
1022 EIC alarms, engine controller
Bit 0 EIC ECU power supp voltage LoLo
Bit 1 EIC Fuel high temp
Bit 2 EIC Exhaust A high temp
Bit 3 EIC Exhaust B high temp
Bit 4 EIC Pressure 1 high (Aux 1)
Bit 5 EIC Pressure 2 high (Aux 2)
Bit 6 EIC Day tank high level
Bit 7 EIC Day tank low level
Bit 8 EIC Run-up speed not reached
Bit 9 EIC Idle speed not reached