Section 75 00-02-0878
2013-03-07 - 123 -
Write Commands to Engine Controller
Engine controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls).
Engine speed
CANbus ID for speed control: 0x0c000000. J1939 TSC1.
M-Logic commands are available to enable/disable start/stop and speed controls.
EIC start/stop enable
EIC speed control inhibit
NOTE: The speed regulation is enabled in parameter 2781 (Reg. output)
and 7563 (EIC Controls).
Cummins CM850-CM570 (J1939)
Warnings and Shutdowns
Warning/shutdown list
J1939
codes
SPN
FMI
warning
FMI
shutdown
Low oil
pressure
100
18
1
Coolant temperature
110
16
0
Oil
temperature
175
16
0
Intake manifold
temp
105
16
0
Fuel temperature
174
16
0
Coolant
level
low
111
18
1
Overspeed
190
-
16
Crankcase pressure high
101
-
0
Coolant pressure low
109
-
1
EIC
yellow
lamp
-
X
-
EIC
red
lamp
-
-
X
EIC malfunction
-
x
-
EIC protection
-
x
-
NOTE: FMI indication “-“ means that the alarm in question is not
supported.