Section 75 00-02-0878
2013-03-07 - 124 -
Write Commands to Engine Controller
Engine Controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls).
M-Logic commands are available to enable/disable speed controls:
EIC Speed Control Inhibit.
Engine Speed
CANbus ID for speed control: 0x00FF69DC. For Cummins proprietary “Engine
governing” EG telegram, the source address of the EMS-GC10 controller is 0xDC/220
dec).
Frequency Selection
Nominal frequency is written automatically based on the frequency nominal parameter.
50 Hz is written if: fNOM is < 55 Hz.
60 Hz is written if: fNOM is > 55 Hz.
Gain setting
Gain is set in parameter 2773.
Shutdown Override
This command can be used in order to prevent shut down actions from the ECU. The
function follows the standard EMS-GC10 function “shutdown override” (digital input on
the EMS-GC10).