Section 75 00-02-0878
2013-03-07 - 130 -
MTU J1939 Smart Connect
Smart Connect
This protocol is available with MTU series 1600 With ECU8/Smart Connect.
Warnings and Shutdowns
Warning/shutdown list
J1939
codes
SPN FMI warning FMI shutdown
EIC yellow lamp
-
X
-
EIC red lamp
-
-
X
EIC malfunction
-
x
-
EIC protection
-
x
-
NOTE: FMI indication “-“ means that the alarm in question is not
supported.
Write Commands to Engine Controller
Engine Controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are
enabled in parameter 7563 (EIC Controls).
Engine Speed
CANbus ID for speed control: 0x0c000000. J1939 TSC1.
M-Logic commands are available to enable/disable start/stop and speed controls:
EIC Start/Stop Enable
EIC Speed Control Inhibit
NOTE: The speed regulation is enabled in parameters 2781 (Reg. output)
and 7563 (EIC Controls).
Frequency Selection
Nominal frequency is written automatically based on the frequency nominal
parameter. 50 Hz is written if f
nominal
<55Hz, 60 Hz is written if f
nominal
is >55 Hz.
Shut down Override
This command can be used with a digital input in order to override shut down actions
from the ECU.
Engine Overspeed Test
The command is activated through M-Logic. Testing of the overspeed function at any
given rpm.
Enable Cylinder Cutout
The command can be used to engage all cylinders if the engine is running with one
bank only. The command is activated through M-logic.