Section 75 00-02-0878
2013-03-07 - 75 -
Full to Fuel Fill Check
The fuel pump logic includes a Fuel fill check function.
When the fuel pump is running, the fuel level must increase by 2% within the fuel fill
check timer set in parameter 6553. If the fuel level does not increase by 2% within the
adjusted delay time, then the fuel pump relay deactivates and a Fuel Fill Alarm occurs.
NOTE:
The
level
of
increase is
fixed at
2% and cannot be changed.
Fail Class
All activated alarms must be configured with a fail class. The fail classes define the
category of the alarms and the subsequent alarm action.
Seven different fail classes can be used. The tables below illustrate the action of each
fail class when the engine is running or stopped.