Section 75 00-02-0878
2013-03-07 - 76 -
Engine Running
Fail Class Action
Alarm Horn
Relay
Alarm
Display
Trip Of Gen.
Breaker
Trip Of Mains
Breaker
Cooling-
Down Genset
Stop
Genset
1 Block X X
2 Warning X X
3 Trip GB X X X
4 Trip + stop X X X X X
5 Shutdown X X X X
6 Trip MB X X X
7 Trip MB/GB X X (X) X
The table illustrates the action of the fail classes. If, for instance, an alarm has been
configured with the "shutdown" fail class, the following actions occur.
The alarm horn relay will activate
The alarm will be displayed in the alarm info screen
The generator breaker will open instantly
The genset is stopped instantly
The genset cannot be started (see next table)
NOTE: The fail class "Trip MB/GB" will only trip the generator
breaker if there is no mains breaker present.
Engine Stopped
Fail Class Action Block Engine Start Block MB Sequence Block GB Sequence
1 Block X
2 Warning
3 Trip GB X X
4 Trip + stop X X
5 Shutdown X X
6 Trip MB X
7 Trip MB/GB (X) X (X)
NOTE:
In
addition
to the
actions
defined
by
the fail
classes,
it
is
possible
to activate
one or two relay outputs
if
additional
relays are
available in
the
unit.
NOTE: The fail class "Trip MB/GB" will only block engine start and
GB sequence if no mains breaker is present.