Section 75 00-02-0878
2013-03-07 - 122 -
Specific Engine Type Descriptions
About Type Descriptions
NOTE: The J1939 warnings/shutdowns with corresponding SPN and FMI
numbers in this chapter refer to those that will automatically appear in the
alarm list. The alarms can be acknowledged from the display.
NOTE: The available alarms vary from engine type to engine type.
Besides these, the entire log list can be read in the engine controller by
holding the “LOG” button for 3 seconds.
Caterpillar/Perkins (J1939)
Warnings and Shutdowns
Warning/shutdown list
J1939 Codes
SPN FMI Warning FMI Shutdown
Low oil pressure 100 17 1
Intake manifold #1 P 102 15 -
Coolant temperature 110 15 1
High inlet air temp. 172 15 -
Fuel temperature 174 15 -
Overspeed 190 15 0
EIC yellow lamp - X -
EIC red lamp - - X
EIC malfunction - X -
EIC protection - X -
NOTE: FMI Indication “- means that the alarm in question is not
supported.