Section 75 00-02-0878
2013-03-07 - 121 -
In both cases the droop function is activated in the M-logic (EIC droop/EIC droop eumulation)
command output.
Please refer to the specific engine type to determine if droop is supported or whether emulated
droop has to be used.
EIC Inhibit
The EIC alarms can be inhibited through M-Logic. This would typically be necessary during
stopping of the engine. The following alarms can be inhibited:
• EIC red alarm
• EIC yellow alarm
• EIC malfunction
• EIC protection
EIC Idle
The “Idle” function of the EMS-GC10 is activated in parameter 6290. If this is used with
engines with speed control from CANbus communication, the speed is defined to be 700 rpm.