Digital Inputs
The unit has a number of binary inputs, some are configurable and some are not.
Input Function
Auto
Semi
Test
Man
Block
Configurable
Input Type
1
Shutdown override
X
X
X
X
X
Configurable
Constant
2
Access lock
X
X
X
X
X
Configurable
Constant
3
Binary running detection
X
X
X
X
X
Configurable
Constant
4
Remote start
X
X
Configurable
Pulse
5
Remote stop
X
X
Configurable
Pulse
6
Test
X
X
X
X
Configurable
Pulse
7
Auto
X
X
X
X
Configurable
Pulse
8
Manual
X
X
X
Configurable
Pulse
9
Block
X
X
X
X
Configurable
Constant
10
Remote GB ON
X
X
Configurable
Pulse
11
Remote GB OFF
X
X
Configurable
Pulse
12
Remote MB ON
X
X
Configurable
Pulse
13
Remote MB OFF
X
X
Configurable
Pulse
14
Remote alarm acknowledge
X
X
X
X
X
Configurable
Constant
15
Auto start/stop
X
Configurable
Constant
16
Remove starter
X
X
X
X
Configurable
Constant
17
GB position ON
X
X
X
X
X
Configurable
Constant
18
GB position OFF
X
X
X
X
X
Configurable
Constant
19
MB position ON
X
X
X
X
X
Configurable
Constant
20
MB position OFF
X
X
X
X
X
Configurable
Constant
21
Emergency stop
X
X
X
X
X
Not configurable
Constant
22
Low speed
X
X
X
Configurable
Constant
23
Temperature control
X
X
X
Configurable
Constant
24
Battery test
X
X
Configurable
Pulse
25
Mains Okay
X
X
X
X
X
Configurable
Pulse
26
GB close inhibit
X
X
X
X
Configurable
Constant
27
MB close inhibit
X
X
X
X
X
Configurable
Constant
28
Enable mode shift
X
X
X
X
X
Configurable
Constant
29
Start enable
X
X
X
X
Configurable
Constant
30
Alternative start
X
X
X
X
X
Configurable
Constant
31
Switchboard error
X
X
X
X
X
Configurable
Constant
32
Total test
X
X
X
X
X
Configurable
Constant
33
GB spring loaded
X
X
X
X
X
Configurable
Constant
34
MB spring loaded
X
X
X
X
X
Configurable
Constant
35
D+ (digital running feedback)
X
X
X
X
X
Configurable
Constant
36
Inhibit Engine alarms
X
X
X
X
X
Configurable
Constant