Section 75 00-02-0878
2013-03-07 - 81 -
Functional Description—Input
1. Shutdown override
This input deactivates all protections except the over speed protection and the
emergency stop input. The number of start attempts is seven by default, but it can be
configured in parameter 6201. Also a special cool down timer is used in the stop
sequence after an activation of this input.
2. Access lock
Activating the access lock input deactivates the control display push-buttons. It will only
be possible to view measurements, alarms and the log.
3. Binary running detection
The input is used as a running indication of the engine. When the input is activated, the
start relay is deactivated.
4. Remote start
This input initiates the start sequence of the genset when semi-auto or manual mode is
selected.
5. Remote stop
This input initiates the stop sequence of the genset when semi-auto or manual mode is
selected. The genset will stop without cooling down.
6. Test
Changes the present running mode to test.
7. Auto
Changes the present running mode to auto.
8. Manual
Changes the present running mode to manual.
9. Block
Changes the present running mode to block.
NOTE: When block mode is selected, the running mode cannot be
changed by activating the digital inputs.
10. Remote GB ON
The generator breaker ON sequence will be initiated and the breaker will close if the
mains breaker is opened.
11. Remote GB OFF
The generator breaker OFF sequence will be initiated.