Section 75 00-02-0878
2013-03-07 - 119 -
Caterpillar/Perkins
Caterpillar and Perkins have a primary and a secondary DM1 log as well as one DM2 log. Use
the up or down buttons until the “2
nd
DM1 log” is shown and press enter. The second
alarm log will be shown in the display.
Example:
2
nd
DM1 Caterpillar
Oil pressure
SlightlyAboveRange
SPN 100
FMI 15
The primary DM1 log shows alarms from the ADEM III/IV engine controllers. The secondary
DM1 log shows alarms from the EMCP 3.x gen-set controller. Similar to the J1939 protocol the
DM2 log shows the historical alarms. Use the up and down buttons to scroll through
the list.
NOTE: The display of Caterpillar/Perkins secondary DM 1 log only applies
to EMS-GC10 100 and GC-1F/2.
Control Commands Sent to the Engine
Engine types with the possibility to send commands to the ECM via the CANbus
communication line:
Engine Type
Detroit
Diesel
John
Deere
Caterpillar Perkins Cummins
Generic
J1939
Deutz EMR Iveco
Iveco
Vector
Command
Preheat - - - - - - - - -
Start/Stop - - X X - - - - -
Engine Speed X X X X X/ X X X X
Nominal Frequency - - - - X - - - -
Governor gain - - - - X - - - -
Idle speed X X X X X X X X -
Droop - - X X X - - - -
Shutdown override - - - - X - - - -
Engine overspeed test - - - - - - - - -
Enable cylinder cut out - - - - - - - - -
Intermittent oil priming - - - - - - - - -
Engine operating mode - - - - - - - - -
Demand switch - - - - - - - - -
Trip counter reset - - - - - - - - -
Engine speed GOV parameter
- - - - - - - - -