Section 75 00-02-0878
2013-03-07 - 20 -
Running Mode Description
Manual Mode
The unit can be operated in manual mode (MAN). Manual means that the unit will not
initiate any sequences automatically, as is the case with the auto mode. It will only
initiate sequences, if external signals are given.
An external signal may be given in three ways:
1. Start and Stop and MAN push-buttons on the display are used
2. Digital inputs are used
3. Modbus command at service port or RS 485
NOTE: The standard EMS-GC10 is only equipped with a limited
number of digital inputs, please see "Digital inputs" in this
document for additional information about availability.
The following sequences can be activated in manual mode:
Command
Description
Comment
Start
The start sequence is initiated and continues until the genset starts or
the maximum number of start attempts has been reached.
First start: include
preheat
Second start: cancel
preheat
Stop
The genset will be stopped. After disappearance of the running signal,
the stop sequence will continue to be active in the ‘"extended stop
time" period. The genset is stopped with cooling down time.
The cooling down
time is cancelled if
the stop button is
activated twice.
Close GB
The unit will close the generator breaker if the mains breaker is open
Open GB
The unit will open the generator breaker instantly
Close MB
The unit will close the mains breaker if the generator breaker is open
Open MB
The unit opens the mains breaker instantly.