Section 75 00-02-0878
2013-03-07 - 17 -
Single Phase System
The single phase system consists of one phase and the neutral.
The following adjustments must be made to make the system ready for the single
phase measuring (example 230V AC):
value
Phase-neutral voltage of the generator
Primary voltage of the G voltage transformer (if installed)
Secondary voltage of the G voltage transformer (if installed)
Primary voltage of the BB voltage transformer (if installed)
Secondary voltage of the BB voltage transformer (if installed)
Phase-phase voltage of the busbar
NOTE: The voltage alarms refer to UNOM (230V AC).
NOTE: EMS-GC10 unit has two sets of BB transformer settings,
which can be enabled individually in this measurement system.
Split Phase System
When EMS-GC10 unit is delivered from the factory, the three-phase system is selected.
When this principle is used, all three phases must be connected to the EMS-GC10
controller unit.
The following adjustments must be made to make the system ready for the three-phase
measuring (example 400/230V AC):
value
Phase-phase voltage of the generator
Primary voltage of the G voltage transformer (if installed)
Secondary voltage of the G voltage transformer (if installed)
Primary voltage of the BB voltage transformer (if installed)
Secondary voltage of the BB voltage transformer (if installed)
Phase-phase voltage of the busbar
NOTE: EMS-GC10 has two sets of BB transformer settings, which
can be enabled individually in this measurement system.