Section 75 00-02-0878
2013-03-07 - 39 -
Start Sequence Conditions
The start sequence initiation can be controlled by the following conditions:
• (oil pressure)
• (water temperature)
• (fuel level)
This means that if, for example, the oil pressure is not primed to the sufficient value,
then the crank relay will not engage the starter motor.
The selection is made in parameter 6185. For each of the Analog Input settings, the
rule is that the value (oil pressure, fuel level or water temperature) must exceed the
setpoint of setting 6186 before starting is initiated.
NOTE: If the value in parameter 6186 is set to 0.0, the start
sequence is initiated as soon as it is requested.
The diagram below shows an example where the analog input signal builds up slowly,
and starting is initiated at the end of the third start attempt.