Section 75 00-02-0878
2013-03-07 - 53 -
Oil Pressure
The multi-inputs on terminals 6, 7 and 8 can be used for the detection of running
feedback. The terminal in question must be configured as an analog input for oil
pressure measurement.
When the oil pressure increases above the adjusted value, (parameter 6175 Pressure
level), the running feedback is detected, and the start sequence is ended.
Running Feedback
Remove Starter Input
The drawing below shows how the setpoint of the "remove starter input" is detected at
the firing speed level. The factory setting is 400 RPM (parameter 6170 Running detect).
NOTE: The remove starter function can use the MPU or a digital
input.