Section 75 00-02-0878
2013-03-07 - 57 -
Island Mode Condition
The diagram shows an example where a single EMS-GC10 in Island Mode is controlled
by the AUTO start/stop input.
This is what happens: When the AUTO start/stop input deactivates, the GB opens. The
AUTO start/stop is reactivated immediately after the GB has opened, for example, by
the operator through a switch in the switchboard. However, the EMS-GC10 unit waits a
while before it issues the close signal again, because the spring load time must expire
(or the digital input must be activated - not shown in this example). Then EMS-GC10
unit issues the close signal.