Section 75 00-02-0878
2013-03-07 - 59 -
Selections for Alarm Inhibit:
Function
Description
Inhibit 1
M-Logic outputs: Conditions are programmed in M-Logic
Inhibit 2
Inhibit 3
GB ON ( ON)
The generator breaker is closed
GB OFF ( ON)
The generator breaker is open
Run status
Running detected and the timer in parameter 6160 expired
Not run status
Running not detected or the timer in parameter 6160 not expired
Generator voltage > 30%
Generator voltage is above 30% of nominal
Generator voltage < 30%
Generator voltage is below 30% of nominal
MB ON
The mains breaker is closed
MB OFF
The mains breaker is open
NOTE: The timer in parameter 6160 is not used if binary running
feedback is used.