Section 75 00-02-0878
2013-03-07 - 67 -
Idle Speed, No Stopping
In this example both timers are deactivated.
If the genset is to be prevented from stopping, then the digital input "temp control" must
be left ON at all times. In that case the characteristic looks like this.
NOTE: The oil pressure alarm (analog input for oil) will be enabled
during idle run if set to "ON".
Inhibit
The alarms that are deactivated by the inhibit function are inhibited in the usual manner,
except for the oil pressure alarms; Input oil using RMI 6,7 or 8 which are active during
"idle run" as well.
Running Signal
The running feedback must be activated when the genset is running in idle mode.
Idle speed flowcharts
The flowcharts illustrate the starting and stopping of the genset by use of the inputs
"temp control" and "low speed".