Section 75 00-02-0878
2013-03-07 - 70 -
Engine Heater
This function is used to control the temperature of the engine. A sensor measuring the
cooling water temperature is used to activate an external heating system to keep the
engine at a minimum temperature.
The setpoints adjusted in parameter 63206324, 6330 are:
Parameter 6321 setpoint
This setpoint +/- the hysteresis is the start and stop points
for the engine heater.
Output A
The relay output for the engine heater.
Input type
Multi-input to be used for temperature measurement.
Hysteresis
This decides how big a deviation from the setpoint is
needed to activate/deactivate the engine heater
Enables
Enables the engine heater function.
Principle Diagram
:
NOTE: The engine heater function is only active when the engine
is stopped.
Engine Heater Alarm
If the temperature keeps dropping after the start setpoint has been exceeded, an alarm
will be raised if configured in parameter 6330.