Section 75 00-02-0878
2013-03-07 - 72 -
The drawing below shows that when the test is started, the start relay activates making
the engine turn.
Input Configuration
If this function is to be used, it is necessary to configure a digital input that
initiates the function. Using the PC software (USW), this is done in the
`dialogue box below:
If AUTO mode is selected, the mains failure sequence will be
initiated if a mains failure occurs during the battery test.
Auto Configuration
If the automatic battery test is used, the function has to be enabled in parameters 6420,
6421, 64236425. When the function is enabled, the battery test will be carried out with
a specified interval, for example, once a week. Completed battery tests will be logged in
a separate battery test log.
The factory setting in parameter 6424 is 52 weeks. This means,
that the automatic battery test will be executed once a year.