Section 75 00-02-0878
2013-03-07 - 91 -
Scaling Of 4-20 Ma Inputs
The scaling of the analog inputs is made to ensure that the readout of the inputs is
made with a resolution that fits the connected sensor. It is recommended to follow the
guide below when changing the scaling of the analog inputs.
Scaling Example:
1. Use the PC utility software (USW) to configure a multi input to be 4-20mA, in this
example multi input 6 (parameter 10980).
NOTE: Multi input 7 (parameter 10980) and Multi input 8
(parameter 11000)
2. Read the parameters from the device
3. After reading the parameters the 4-20mA alarm appears under the analog window
pane in the USW. The example below shows how to adjust the analog input alarm. The
three dots to the left of the figures, marked with arrows, are buttons. Adjust the input as
required, for example, 0-5 bar: