GT10 Configuration Settings
GT10/GT30
101
5.3 Entering Configuration Settings from the GT10 Main Unit
5.3.6 Setting Mode: “Memory Initialization” (Clear Memory)
Touching [Setting] on the initial screen of the system menu and then the [Memory] key
of the setting mode menu displays the memory initialization screen. The internal user
memory of the GT10 is initialized here.
Memory initialization screen
Procedure for bringing up the screen
[Initial screen]
↓
[Setting]
↓
[Memory]
Touching the [SRAM] key deletes clock data and Hold PLC Device data held in the
SRAM.
Touching the [FROM] key deletes screen data and main unit configuration settings
saved to the main unit user memory (F-ROM).
When either of the above keys is touched, a confirmation message reading
is displayed. To clear the data, touch the key. A buzzer
sounds, and the memory is cleared. When the buzzer stops sounding, the memory has
been completely cleared.
Learning the shortcut keys saves time!
[RETURN]To complete the settings and return to the previous screen,
touch the [ESC] key.
CAUTION
•
[SRAM] initialization deletes the Hold PLC Device
data backed up in the SRAM. Please be sure that you want
to do this before initializing the SRAM.
•
[FROM] initialization deletes the base screen data, the main unit
configuration setting data (the main unit configuration
setting data returns to the default values) and contrast
adjustment setting data (the contrast returns to the default
value) in the user memory (F-ROM) of the main unit. Before
initializing the F-ROM, always save screen data to a floppy
disk or another medium with GTWIN.