Connecting and Communicating with the PLC
GT10/GT30
61
4.8 Connecting the FP-M
4.8 Connecting the FP-M
4.8.1 Connecting to the COM. Port
AIP81842
GT10
FP-M COM. port
GT30
FP-M communication format settings
System register no. Item Value Set System register value
412
Selection of target use of RS232C port Computer link K1
413
Data length 8 bits
K3
Parity check Yes
Parity setting Odd
Stop bits 1 bit
Line return code CR
Start code No STX
414
Baud rate setting 19200 bits/s K0
415
Unit number 1 K1
416
Modem connection No connection H0
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no. Wire color Dot mark
1 Brown Black dot
2 Brown Red dot
3 Yellow Black dot
4 Yellow Red dot
5 Green Black dot
6-- --
7 Green Red dot
8-- --
9-- --
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft