GT10/GT30
Connecting and Communicating with the PLC
50
4.2 Connecting the FP0
4.2 Connecting the FP0
4.2.1 Connecting to the COM. Port
FP0 communication format settings
GT30
Loose-wire connection
FP0 COM. port
GT10
System register no. Item Value Set System register value
412
Selection of target
use of RS232C port
Computer link K1
413
Data length 8 bits K3
Parity check Yes
Parity setting Odd
Stop bits 1 bit
Line return code CR
Start code No STX
414
Baud rate setting 19200 bits/s H0 * 00
415
Unit number 1 K1
416
Modem connection No connection H0
Connecting to the FP0 COM. port
GT10
FP0
SSD
RRD
GSG
PLC side
Pin no.
Abbreviation
SD SD
RD RD
RS RS
CS CS
GND GND
GT main unit side
Pin no. Abbreviation
←To set 19200 bits/s
for both the COM.
port and the TOOL
port, “H0100”
should be set.