Connecting and Communicating with the PLCGT10/GT30
47
4.1 Connecting the FP
Σ
4.1 Connecting the FPΣ
4.1.1 Connecting to the COM. Port
Loose-wire connection
FPΣ COM. port
GT10
GT30
RS232C
FPG-COM1
SGCSRSRDSD
AFPG801
MODE
1234
ON
OFF
COM. (RS232C)
SD
RD
RS
CS
GND
TOOL (RS232C)
24V
FPΣ communication format settings
When using COM. Port 1
When using COM. Port
2
System
register no.
Item Value Set System
register no.
Item Value Set
410
COM. Port 1
Unit number
1
411
COM. Port 2
Unit number
1
412
COM. Port 1
Communication
mode
Computer link
No modem
connection
412
COM. Port 2
Communication
mode
Computer link
No modem
connection
413
Data length 8 bits
414
Data length 8 bits
Parity check Yes, Odd Parity check Yes, Odd
Stop bits 1 bit Stop bits 1 bit
Linereturncode CR Linereturncode CR
Start code No STX Start code No STX
415
COM. Port 1
Communication
speed setting
19200 bits/s
415
COM. Port 2
Communication
speed setting
19200 bits/s
Connecting to the FPΣ COM. port
FPΣ
PLC side
SD SD
RD RD
RS RS
CS CS
GND GND
When using the RS232C 1-channel type
Pin no. Abbreviation
SD SD
RD RD
RS RS
CS CS
GND GND
Pin no. Abbreviation
S1 SD
R1 RD
S2 RS
R2 CS
GND GND
Pin no. Abbreviation
SD SD
RD RD
RS RS
CS CS
GND GND
Pin no. Abbreviation
When using the RS232C 1-channel type,
the section between the RS and CS signals
on the PLC side should be shorted.
GT main unit side
PLC side
When using the RS232C 2-channel type
GT main unit side
GT10/GT30