9.3 Error Codes and How to Handle Them
When connected to a PLC (FX) series made by Mitsubishi Electric
The following four types of error codes are displayed when there is an error in the GT
main unit:
Code no. Content Cause and solution
FF
Time up error
Noresponsefrom the PLC.
Check the connection cable to make sure it is connected.
10
Data error
A data error occurred dur-
ing communication.
Check to see if there is an error in the communication parameters
settings.
12
Overrun error
The GT main unit cannot
receive data.
The problem may be caused by a runaway PLC.
61
PLC error
A NAK error has been re-
turned by the PLC.
Check the PLC settings.
Connecting to a PLC made by Omron
The following three types of error codes are displayed when there is an error in the GT
main unit:
Code no. Content Cause and solution
00
Time up error
Noresponsefrom the PLC.
Check the connection cable to make sure it is connected.
10
Data error
A data error occurred dur-
ing communication.
Check to see if there is an error in the communication parameters
settings.
12
Overrun error
The GT main unit cannot
receive data.
The problem may be caused by a runaway PLC.
Error codes other than the above correspond to error codes for an Omron PLC.