5.11. SAVING, LOADING THE CONFIGURATION OF THE MultiCONT
Settings of the MultiCONT are stored in a non-volatile FLASH memory (FMA). The content of this FLASH memory is replaced into the operative memory (OM) (which
is a volatile memory) when MultiCONT is turned ON or restarted. Settings are saved automatically when exiting from the Menu.
In addition to this, working hours and the switching number of the relays are saved in every 6 minutes into the FLASH memory. In the “Main menu”/”Save config.”
menu point a safety copy (FMS) can be made from the automatically saved settings.
Load of the safety copy can be performed in the “Main menu”/”Load config.” menu point. When turning ON or restarting, memory content is replaced into the
operative memory from the FLASH memory, if it is faultless (calculated and stored CRC are the same). If there is a safety copy from the settings, the content of this
(FMS) is copied to the operative memory (OM) and the automatic saving storage (FMA) FLASH memory, when ESC and buttons are pressed simultaneously.
FLASH
Nem felejt memória
Beolvas:bekapcsolás/
újraindítás, ha nincs hiba
FMA
Automatikus
mentés
FMS
Biztons gi /
beállís mentés
á
RAM ( OM )
Operav memória
A készülék
kikapcsolásakor a
tartalma elvész
Bekapcsolás/újraindításkor
az ESC és egyidej
megnyosa
Automatikus mentés,
menübl kilépéskor
Beállítás mentés
menübl
Beállítás feltöls
menübl