prw2101a0600p_01
96 / 105
9. SERVICING
9.1. BOX MESSAGES:
No. Box Message Explanation
1 No CODE! Secret code is not set
2 In manual prg! The transmitter is under manual programming
4 Already unlocked! No code in the trasnmitter ( i.e. 00000000 )
5 Unlock, please! Secret code needed for modification (see.”Main menu/”MultiCONT config.”/”password”)
6 HART error! Communication error
7 TOT1 cleared! Value of TOT1 deleted
8 TOT2 cleared! Value of TOT2 deleted
9 HART no reply During programming the device does not respond, or bad data
10* HART comm. error Error in HART message (parity, framing, overflow, …)
11* HART logical error Other logical error in HART message
12* HART write protect The parameter cannot be written
13 Unknown dev/comm The address (Long address) in the HART message is not found in the list
14 Parameter saved Successful save of the parameter
15 Save error Error in writing to FLASH memory
16 Device added The selected device in the „Device detect” menu has been included into the list.
18 Unknown param. Unknown parameter during device detection
19 Default loaded Loading of Factory default ( depending on type ) was successful.
20 PSW cleared Secret code is deleted
23 FLASH error FLASH error at boot
24 Same address! Multiple same Long address found during DEV detect
25 No HART device In the „Device detect” menu, searched for devices with „Short addr.” between 0..15 but did not find any
26 Load error Error when reading from FLASH memory
28 No comp. Device Device is not NIVELCO compatible
30 HART:Parse error The received data are not applicable
31 HART:Invalid sel. The received HART command is unknown to the MultiCONT