prw2101a0600p_01
93 / 105
*** A special error message belongs to sensor failures. This error can appear in
the case of ultrasonic transmitters due to the breakdown of the transducer or
during a dusty filling process, when if there is a display, a NoEcho message is
displayed. In case of magnetostrictive transmitters, this error can be due to the
cracking of the magnet disc, or a break in the magnetostrictive wire.
1: SE300-12 M DIST
2 Errors: 1
SENSERR
Err00
Device responds but there is no
valid result because of sensor
error.
**** Programming error will be caused if:
assignment of more than one source with different dimensions to a relay or current output
an appropriate value (PV, SV, etc) is assigned to a current output and CP1=CP2 (see 5.8 Operation and parameters of current outputs)
assignment of flow value (Impulse F) to a relay and there is more than one source (see 5.7 Relay configuration)
assignment of flow value (Impulse F) to a relay and RP3=0 (see 5.7 Relay configuration)
more than 8 relays with „Alt S” or Sequential function are assigned to a transmitter
different variables are selected in the case of a relay with „Alt R” function
the source is SV, TV or QV, but the COM3 HART command is not selected
ALARM, G function is selected, but the dimensions of the measured values are not the same