9 Tabular overview of the program procedures Discharge
54 © Nortec Electronics 2018
9.1.3 Program 011: Discharge Pb battery sealed commercial
11: Pb battery sealed commercial
select Batteryprocessing:
P0: Discharge
Enter:
Nominal voltage
Rated capacity
Step 1:
Discharging with C
10
until a voltage of 1.8 V for each cell is reached.
End of program
Example:
A 12 V battery with 100 Ah is connected.
The battery will be discharged 10 A to 10.8 V.
Attention! Some battery manufacturers call the criteria for shut down 80 %-limit which means just
80 % capacity of the battery can be taken out of the battery without damaging it.
Time monitoring:
Discharging maximum 12 hours.
9.1.4 Program 016: Discharge Pb battery vented commercial
16: Pb battery vented commercial
select Batteryprocessing:
P0: Discharge
Enter:
Nominal voltage
Rated capacity
Step 1:
Discharging with C
20
until a voltage of 1.8 V for each cell is reached.
End of program
Example:
Connected is a 12 V battery with 100 Ah. The battery will be discharged with 5 A to 10.8 V.
Attention! Some battery manufacturers call the criteria for shut down 80 %-limit which means just
80 % capacity of the battery can be taken out of the battery without damaging it.
Time monitoring:
Discharging maximum 24 hours.