9 Tabular overview of the program procedures Maintenance
© Nortec Electronics 2018 85
9.5 Maintenance
With the help of the program „Maintenance “ the capacity of the lead acid and NiCd batteries will
be tested. For NiCd-batteries the program „P3: Capacity Test“ according to manufaturers instruc-
tions is available in addition.
Example:
Lead battery
================================
COPYRIGHT NORTEC
2014-15 UL60 V 1.0 16.06.15
SN: 160001
--------------------------------
DATE: 28.01.14
BATTERY NO:
OPERATOR NO:
NOM. VOLTAGE: 12.00 V
RATED CAP: 100.0 Ah
PROGRAM: 410
Pb battery sealed MIL
Maintenance
--------------------------------
PROGRAM START 12:07:46
VOLTAGE = 12.81 V
--------------------------------
P410:S1: 16:42:46
DISCHARGE 1
VOLTAGE = 09.00 V
CURRENT = 20.01 A
CAPACITY = 091.4 Ah
= 091 %
TIME = 274 MIN
--------------------------------
P410:S2: 16:45:53
PTOPPING CHARGE 1
VOLTAGE = 14.40 V
CURRENT = 40.01 A
CAPACITY = 002.0 Ah
= 002 %
TIME = 003 MIN
--------------------------------
P410:S3: 18:35:18
I-CHARGE 1
VOLTAGE = 14.40 V
CURRENT = 40.01 A
CAPACITY = 74.70 Ah
= 074 %
TIME = 111 MIN
--------------------------------
P410:S4: 20:04:58
U-CHARGE 1
VOLTAGE = 14.40 V
CURRENT = 02.01 A
CAPACITY = 091.7 Ah
= 091 %
TIME = 201 MIN
Only for deep discharged batteries
--------------------------------
P410:S5: 22:04:25
TOPPING CHARGE 1
VOLTAGE = 14.40 V
CURRENT = 00.71 A
CAPACITY = 094.0 Ah
= 094 %
TIME = 120 MIN
--------------------------------
P410:S6: 02:46:41
DISCHARGE 2
VOLTAGE = 09.01 V
CURRENT = 20.01 A
CAPACITY = 093.9 Ah
= 093 %
TIME = 282 MIN
--------------------------------
P410:S7: 04:42:00
I-CHARGE 2
VOLTAGE = 14.39 V
CURRENT = 40.01 A
CAPACITY = 076.6 Ah
= 076 %
TIME = 114 MIN
--------------------------------
P410:S8: 06:09:53
U-CHARGE 2
VOLTAGE = 14.40 V
CURRENT = 02.01 A
CAPACITY = 093.7 Ah
= 093 %
TIME = 201 MIN
--------------------------------
P410:S9: 08:09:01
TOPPING CHARGE 2
VOLTAGE = 14.40 V
CURRENT = 00.68 A
CAPACITY = 095.9 Ah
= 095 %
TIME = 120 MIN
--------------------------------
BATTERY EVALUATION
C>80%: Battery is OK
CAPACITY = 093.9 Ah
= 093 %
PROGRAM AUTOMATICALLY FINISHED
================================
Example:
NiCd-battery

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nortec UL60 and is the answer not in the manual?

Nortec UL60 Specifications

General IconGeneral
BrandNortec
ModelUL60
CategoryBattery Charger
LanguageEnglish

Related product manuals