9 Tabular overview of the program procedures Maintenance
90 © Nortec Electronics 2018
9.5.4 Program 417: Maintenance Lead Battery P3-C Orion
17: Lead Battery P3-C Orion
Select Batteryprocessing:
P4: Maintenance
Enter:
None, nominal voltage and capacity are preselected by the program
Step 1:
Discharging with C
1
until a voltage of 1.5 V is reached.
Step 2:
I-charge with C
5
for 5 hours (limit 2.375 V/cell).
Step 3:
I-charge with C
10
for 2.5 hours (limit 2.375 V/cell).
Step 4:
Discharging with C
1
to 1.5 V for each cell. The here detected capacity will be used to ascertain the
effective capacity.
Step 5: (not applicable if capacity is below 100 %)
I-charge with C
5
for 5 hours (limit 2.375 V/cell).
Step 6: (not applicable if capacity is below 100 %)
I-charge with C
10
for 2.5 hour (limit 2.375 V/cell).
End of program
Display battery evaluation:
C>100%:BATTERY IS OK
or
C<99%:BATTERY WITH RECORD TAKE DISCHARGED BATTERY OUT OF SERVICE